The ATC-300+ is a comprehensive and multifunctional microprocessor-based ATS controller. It is a compact and self-contained panel-mounted device that is designed to replace traditional relay and solid-state logic panels. The ATC-300+ Controller provides programmed flexibility to address the needs of any system. It operates from all system voltages between 120 to 600V, single-phase and three-phase at 50 or 60 Hz. In addition, a period of no control power is provided. The controller monitors the condition of the three-phase line-to-line voltage and frequency of Source 1 and Source 2 power sources and can be programmed for single-phase operation. The ATC-300+ Controller provides the intelligence to ensure that the ATS operates properly through a series of programmed sensing and timing functions.
Auxiliary relay contacts: Source 1 present 2NO and 2NC Source 2 present 2NO and 2NC Source 1 and…
Specification | Value |
Rating Range | 120 to 600V, single phase and three phase @ 50/60 Hz |
Transfer Type | Switch application dependent |
Switch Type | Switch application dependent |
Specification | Value |
Input Control Voltage | 65 to 145 Vac 50/60 hZ |
Voltage Measurements of Utility | Source 1 VAB Source 2 VAB<br>Source 1 VAC Source 2 VBC<br>Source 1 VCA Source 2 VCA |
Voltage Measurement Range | 0 to 790 VAC rms (50/60 Hz) |
Voltage Measurement Accuracy | +/-2% of nominal input voltage |
Frequency Measurements Of | Source 1 and Source 2 |
Frequency Measurement Range | 40 Hz to 70 Hz |
Frequency Measurement Accuracy | +/- 0.1 Hz |
Undervoltage Dropout | 50% to 90% of nominal voltage |
Undervoltage Pickup | (Dropout +2%) to 99% of the nominal system voltage |
Underfrequency Dropout Range | 90 to 97% of the nominal system frequency |
Underfrequency Pickup Range | (Dropout +1 Hz) to 99% of the nominal system frequency |
Overfrequency Dropout Range | 103 to 110% of the nominal system frequency |
Overfrequency Pickup Range | 101% to (dropout - 1 Hz) of the nominal system frequency |
Operating Temperature Range | -20 to 70 degree C (-4 to +158 degree F) |
Storage Temperature Range | -30 to 85 degree C (-22 to +185 degree F) |
Operating Humidity | 0 to 95% relative humidity (noncondensing) |
Operating Environment | Resistant to ammonia, methane, nitrogen,hydrogen and hydrocarbons |
Generator Start Relay | 5A, 1/6 hp @ 250 Vac Vac 5A @ 30 Vdc with a 150W maximum load |
K1, K2 Relays | <br>10A, 1-3 hp @ 250 Vac</br><br>10A@30 Vdc</br> |
Applicable Testing | UL-recognized component<br>Meets intent of UL 991 & UL 1008<br>Meets IEC 1000-4-2, 1000-4-3, 1000-4-4 |
Applicable Testing Continued | 1000-4-5, 1000-4-6, 1000-4-11<br>CISPR 11, Class A<br>FCC Part 15, Class A<br>CSS 22.2-178 |
Enclosure Compatibility | NEMA 1, NEMA 3R and NEMA 12<br>UV-resistant ATC-300+ faceplate |
Learn more information about the Cat ATC-300+ CONTROLLER.
Download (2.22 MB, PDF)From pre-purchase consults to end-of-lifecycle benefits, Mantrac informs, advises and partners with you.
Speak with the Sales Team to learn the latest prices and information on products that can deliver value and help transform your business.
Find the perfect machine or equipment solution by contacting one of our local specialists. They are on standby, ready to help you solve your operational challenges.
Shanghai Offshore Office
Minhang District, Shanghai, China